For instrument technicians and automation engineers

From number to decision, right in the field.

The calculators and sheets instrument technicians use every day — 4⁠–⁠20 mA, DP range, PT100, thermocouple, PID tuning and calibration — explaining every result: what it means, whether it is within range and what to program into the device.

  • NIST ITS-90
  • IEC 60751
  • NAMUR NE 43
  • PT · EN · ES

See it working

Drag the level. The transmitter responds.

This is the DP range diagram: HP and LP taps, dry or wet leg and the 4–20 mA signal calculated instantly, with the same numbers as the tool.

LRV · 4 mA
0 kPa
URV · 20 mA
29.42 kPa
DP
18.24 kPa
Signal
13.92 mA
Open the DP range tool
Installation diagramTank with the HP tap at the 0% level. In a closed tank, the LP tap is in the vapor space, above 100%. Educational diagram, not to scale.100% · URV50%0% · LRV62%Lower tap · HPUpper tap · LPDry legDPHPLPh = 1.86 mH = 3 mHP elevation offset: 0 m

Drag the level in the tank or use the slider below. The upper LP tap remains in the vapor space, above the 100% level. Educational diagram, not to scale.

Why ALOGY Tools

A calculator shows a number. A technician needs a decision.

Understand what the number means

Within range, saturation, transmitter failure or reversed polarity: the reading comes with a field interpretation, not just a value.

Program it right the first time

LRV and URV for the DP transmitter, and Kp, Ti and Td in the form, unit and scale your PLC or controller uses.

Document without rework

PDF reports and calibration sheets with no logo or advertising, ready to attach to the customer job.

How it works

A workflow built for field work.

  1. 01

    Calculate

    The right calculation, with explicit units and range.

  2. 02

    Check

    Tables, limits and the formula used, always in view.

  3. 03

    Understand

    What the number means: within range, saturation or failure.

  4. 04

    Simulate

    Watch the loop respond before touching the plant.

  5. 05

    Document

    Unbranded PDF reports and sheets, ready for the customer.

  6. 06

    Apply

    Values in the convention of your PLC, transmitter or controller.

PID tuning

The PID you program, not just the one you calculate.

  • Gain in engineering units, dimensionless (%/%) or proportional band, from the block ranges.
  • Ideal, series or parallel form, with Ti in seconds, minutes or repeats per minute.
  • Simulation with SP, PV, output, P/I/D contributions, saturation and anti-windup.
  • Compare with the parameters already in the device before changing them.
Open PID tuning

4–20 mA

The reading comes with a diagnosis.

  • 12.43 mA = 52.7% of range ≈ 263.4 °C, in one sentence.
  • Negative current? Leads reversed. Zero? Open loop.
  • With NAMUR NE 43: failure ≤ 3.6 mA or ≥ 21 mA, saturation and undefined bands.
  • LL, L, H and HH thresholds in engineering units, including reverse scales.
Open the 4–20 mA calculator

Verifiable accuracy

Technical accuracy comes first.

Primary references

Thermocouples from the NIST ITS-90 coefficients, checked against the official tables; PT100 by Callendar–Van Dusen and IEC 60751 classes.

Automated tests

More than 90 tests with reference values, limits, reverse ranges and invalid inputs protect every calculation.

Technical honesty

Formulas and assumptions visible on every screen. An empty field never becomes zero, and the tool warns when a number does not represent the process.

Built for the phone

One hand and gloves: large controls, a +/− key for negatives and readable text on phones.

Your data, your device

Calculations on the device; sheets with a local draft and file backup.

Three languages

Portuguese, English and Spanish on screens, help and reports.

Plans

The same tools on every plan.

INDIVIDUAL ACCESS

Tools Monthly

R$19.90/month

Just the tools, renewed monthly.

INDIVIDUAL ACCESS

Tools Annual

R$149/year

Works out to R$12.42 a month: R$89.80 less per year than monthly.

Individual plans with Pix or card. Sign-up when sales open.

Questions

Frequently asked questions

Does the report replace a calibration certificate?

No. The tools document calculations and data collection. They state what they do not do: they declare no conformity, uncertainty or traceability without the data from your procedure.

Can I apply the PID tuning straight to the PLC?

It is a starting point calculated from the process model, with simulation and values in the device convention. Applying it to the plant requires an authorised test and monitoring of the loop.

Do Instrumentation Guide buyers get access?

Yes. Buying the Instrumentation Guide on Hotmart includes 1 year of ALOGY Tools, with the same tools as the individual plans. Past buyers of the Guide get it too, with the year counted from when sales open. Renewal at the end is optional.

Does my data go to a server?

Calculations run on your device. Sheet drafts stay in your browser, with a file backup you control.

Does it work on a phone, in the field?

Yes. Screens are designed for one hand and gloves: 44 px touch targets, a +/− key for negative values and text of at least 12 px on phones.

Do I need an internet connection?

To open the tool, yes. Once open, every calculation happens on the device itself.

In which languages?

Portuguese, English and Spanish: screens, help and reports.

Got an instrumentation problem? Open ALOGY Tools.

Open the tools