4–20 mA calculator: current, percent and process value
Convert a 4–20 mA loop current into percent and process value, or go the other way to simulate a transmitter. The reading comes interpreted: within range, saturation or failure signal per NAMUR NE 43, with square root for differential-pressure flow.
Where it helps at work
- Check in the field, with the meter in series, whether the transmitter current matches the SCADA value.
- Know how many mA to inject with the calibrator to simulate 0, 25, 50, 75 and 100 % of range at the PLC card.
- Understand a reading outside 4–20 mA: saturation, a failure signalled by the transmitter or an open loop.
- Convert the signal of an orifice-plate flow transmitter, with square-root extraction.
Worked example: reading a pressure transmitter at the PLC
A pressure transmitter calibrated from 0 to 16 bar is wired to the PLC analog input card. With the meter in series in the loop, the reading is 11.2 mA.
| Calibrated range | 0 to 16 bar |
|---|---|
| Measured current | 11.2 mA |
| Characteristic | Linear |
| Percent of range | 45 % |
|---|---|
| Engineering value | 7.2 bar |
| Sensitivity | 1 bar/mA |
| Reading status | Within range |
How to read it
11.2 mA is 45 % of the range, that is, 7.2 bar. On this range, each milliampere is worth 1 bar: a 0.1 mA error in the reading already means 0.1 bar in the process. The current is within 4–20 mA, so the value is a real measurement; if the SCADA shows another number, check the range set in the transmitter and in the PLC before blaming the instrument.
Limits and cautions
- It converts the signal; it does not measure or calibrate: accuracy depends on the meter, the calibrator and the transmitter.
- Outside 4–20 mA the engineering value is an extrapolation and does not represent the process when the transmitter signals a failure.
- The NE 43 levels only apply if the transmitter is configured for them; check the manual and the alarm setting.
- It does not assess the loop resistance or the transmitter minimum voltage, which limit the load the supply can drive.
Technical basis
Linear relation between the 4 to 20 mA signal and the calibrated range, square-root extraction for differential-pressure elements (ISO 5167-1) and the signal levels of the NAMUR NE 43 recommendation.
- NAMUR NE 43 — standardization of the signal level for the failure information of digital transmitters
- IEC 60381-1 — analogue direct current signals for process control systems
- ISO 5167-1 — flow measurement by means of differential pressure devices
Frequently asked questions
How do I convert 4–20 mA to percent?
Subtract 4 from the current and divide by 16. With 12 mA, (12 − 4) ÷ 16 gives 0.5, that is, 50 % of range; with 8 mA, 25 %; with 16 mA, 75 %.
How do I go from mA to the process value?
Multiply the percent by the span and add the start of the range (LRV). On a 0 to 16 bar transmitter, 11.2 mA is 45 % of range, or 7.2 bar. When the range does not start at zero, such as −50 to 150 °C, the start goes into the sum.
What does a current below 4 mA or above 20 mA mean?
That the reading left the range. Per NAMUR NE 43, from 3.8 to 20.5 mA the transmitter still reports a measurement, saturated; at 3.6 mA or below, or 21 mA or above, it signals a failure. A current near zero points to an open loop, no supply or a blown fuse.
When should I use the square root?
When the transmitter measures the differential pressure of an orifice plate, venturi or nozzle and the root is not extracted in the transmitter or in the PLC. Flow is proportional to the root of the differential: 8 mA (25 % of the differential) is 50 % of flow.
Why does the signal start at 4 mA and not 0 mA?
It is the live zero: with 4 mA at the start of the range, zero current reveals an open loop or missing supply, and a two-wire transmitter still has current to power itself with the process at 0 %.