4–20 mA calculator

Signals and scaling

Convert current, percentage and engineering values in real time.

Saved only in this browser, not in your account

Configuration

Instrument range
Span 10 barIncreasing ↗

Calculate from

mA

Use a comma or decimal point. For negative values, tap +/−.

Use an example range

Use the same endpoints configured in the instrument and PLC.

Conversion result

Live
Current

8.4mA

Percentage

27.5%

Engineering value

2.75bar

Within range · linear conversion

Signal curve

0 to 10 bar
Linear 4–20 mA conversion curvebar02.557.51048121620mA

Explore the signal

Drag or use the arrow keys
4 mA8 mA12 mA16 mA20 mA
Within range · linear conversion

8.4 mA = 27.5% of range ≈ 2.75 bar (range 0 to 10 bar).

Reading within the configured range.

8.4 mA 2.75 bar
Do not use in safety systems (SIS)Limits
  • Do not use it to design or validate safety instrumented functions (SIS/SIL, IEC 61511) or interlocks. Check the scale in the transmitter and in the PLC.
  • Calculated values. These are not calibration measurements.
  • Technical support: check the data you entered. The design, the configuration and the decision to apply the result belong to the responsible professional, with the standard and the manufacturer’s data.

Range table

Reference points for simulation and scale checks.

CurrentPercentageEngineering (bar)Apply point
4 mA0 %0
6 mA12.5 %1.25
8 mA25 %2.5
10 mA37.5 %3.75
12 mA50 %5
14 mA62.5 %6.25
16 mA75 %7.5
18 mA87.5 %8.75
20 mA100 %10
Calculated values. These are not calibration measurements.

More instrumentation tools

This calculator is free. These tools, for the same transmitters and sensors, are part of the ALOGY Tools subscription.

Record the check in the pressure sheetCalibration sheet of the subscription: opens with the range of this loop and converts readings in mA.

All tools for R$19.90 per month or R$149 per year. See the plans

Current8.4 mA
Percentage27.5 %
Engineering2.75 bar

4–20 mA calculator: current, percent and process value

Convert a 4–20 mA loop current into percent and process value, or go the other way to simulate a transmitter. The reading comes interpreted: within range, saturation or failure signal per NAMUR NE 43, with square root for differential-pressure flow.

Where it helps at work

  • Check in the field, with the meter in series, whether the transmitter current matches the SCADA value.
  • Know how many mA to inject with the calibrator to simulate 0, 25, 50, 75 and 100 % of range at the PLC card.
  • Understand a reading outside 4–20 mA: saturation, a failure signalled by the transmitter or an open loop.
  • Convert the signal of an orifice-plate flow transmitter, with square-root extraction.

Worked example: reading a pressure transmitter at the PLC

A pressure transmitter calibrated from 0 to 16 bar is wired to the PLC analog input card. With the meter in series in the loop, the reading is 11.2 mA.

Data
Calibrated range0 to 16 bar
Measured current11.2 mA
CharacteristicLinear
Result
Percent of range45 %
Engineering value7.2 bar
Sensitivity1 bar/mA
Reading statusWithin range

How to read it

11.2 mA is 45 % of the range, that is, 7.2 bar. On this range, each milliampere is worth 1 bar: a 0.1 mA error in the reading already means 0.1 bar in the process. The current is within 4–20 mA, so the value is a real measurement; if the SCADA shows another number, check the range set in the transmitter and in the PLC before blaming the instrument.

Limits and cautions

  • It converts the signal; it does not measure or calibrate: accuracy depends on the meter, the calibrator and the transmitter.
  • Outside 4–20 mA the engineering value is an extrapolation and does not represent the process when the transmitter signals a failure.
  • The NE 43 levels only apply if the transmitter is configured for them; check the manual and the alarm setting.
  • It does not assess the loop resistance or the transmitter minimum voltage, which limit the load the supply can drive.

Technical basis

Linear relation between the 4 to 20 mA signal and the calibrated range, square-root extraction for differential-pressure elements (ISO 5167-1) and the signal levels of the NAMUR NE 43 recommendation.

  • NAMUR NE 43 — standardization of the signal level for the failure information of digital transmitters
  • IEC 60381-1 — analogue direct current signals for process control systems
  • ISO 5167-1 — flow measurement by means of differential pressure devices
How we verify the calculations

Frequently asked questions

How do I convert 4–20 mA to percent?

Subtract 4 from the current and divide by 16. With 12 mA, (12 − 4) ÷ 16 gives 0.5, that is, 50 % of range; with 8 mA, 25 %; with 16 mA, 75 %.

How do I go from mA to the process value?

Multiply the percent by the span and add the start of the range (LRV). On a 0 to 16 bar transmitter, 11.2 mA is 45 % of range, or 7.2 bar. When the range does not start at zero, such as −50 to 150 °C, the start goes into the sum.

What does a current below 4 mA or above 20 mA mean?

That the reading left the range. Per NAMUR NE 43, from 3.8 to 20.5 mA the transmitter still reports a measurement, saturated; at 3.6 mA or below, or 21 mA or above, it signals a failure. A current near zero points to an open loop, no supply or a blown fuse.

When should I use the square root?

When the transmitter measures the differential pressure of an orifice plate, venturi or nozzle and the root is not extracted in the transmitter or in the PLC. Flow is proportional to the root of the differential: 8 mA (25 % of the differential) is 50 % of flow.

Why does the signal start at 4 mA and not 0 mA?

It is the live zero: with 4 mA at the start of the range, zero current reveals an open loop or missing supply, and a two-wire transmitter still has current to power itself with the process at 0 %.