Power electricsSubscription
Industrial cable sizing: the cable based on NBR 5410 from the load and the distance
Enter the load (power or current), the distance to it, the installation method, the grouping and, if you have it, the short-circuit current; for a motor, the start. The tool gives the low-voltage cable (up to 1 kV) based on NBR 5410 (IEC 60364-5-52) — minimum section, current-carrying capacity, voltage drop, drop at start and short circuit —, the breaker with its curve, the neutral, the protective conductor and the length to buy.
Subscription tool
Read the explanation and the example freely. To use the tool with your own data, log in to an account with active access or subscribe.
Read the explanation and the example freely. To use the tool with your own data, log in to an account with active access.
Want to check the quality first? Free, no sign-up: 4–20 mA calculator · residential cable sizing (whole house)
EnlargeWhere it helps at work
- Choose the cable of a motor far from the MCC, in conduit, on a tray or a ladder.
- Size the feeder of a panel with parallel cables.
- Check the section against the short circuit near the transformer.
- Compare copper and aluminium, PVC and XLPE, and document the choice in the report.
What you enter
What you get
Worked example: feeding a 15 kW motor
A 15 kW (shaft) three-phase motor, 380 V, power factor 0.85 and 90 % efficiency, started direct on line (Ip/In = 7), is 50 m from the panel in a TN system. The flexible copper cable with PVC insulation runs alone in a surface conduit (method B1) at 30 °C, and the maximum drop allowed is 4 %. Which cable and breaker?
| System | Three-phase |
|---|---|
| Line-to-line voltage | 380 V |
| Shaft power | 15 kW |
| Power factor | 0.85 |
| Efficiency | 90 % |
| Distance to the load | 50 m |
| Installation | B1 · surface conduit · copper · PVC |
| Drop limit | 4 % |
| Start | Direct on line · Ip/In 7 |
| Design current Ib | 29.8 A |
|---|---|
| Breaker | 32 A · curve D |
| Recommended cable | 10 mm² |
| Corrected capacity Iz | 50 A |
| Voltage drop | 5.15 V (1.35 %) |
| Section by voltage drop | 4 mm² |
| Drop at start | 3.71 % |
| Length protected against shock | 57 m |
How to read it
The design current is 29.8 A and the next standard breaker is 32 A. The voltage drop alone would accept 4 mm² (3.45 % at 50 m), but that cable carries only 28 A in method B1, less than the breaker: the current-carrying capacity asks for 6 mm². At start, with 209 A and cos φ 0.3, the drop reaches 3.71 %, within the 10 % of NBR 5410 (6.5.1.3.3); as curve C would trip from 160 A, less than the start, the breaker is curve D, whose instantaneous trip is only guaranteed from 640 A. With 6 mm², an earth fault at the end of the cable does not reach that current: the breaker protects against shock only up to 33 m (NBR 5410, 5.1.2.2.4.2). The section adopted, the largest of the criteria, is 10 mm², which protects up to 57 m, with an Iz of 50 A and a 1.35 % drop. With an RCD on the circuit, 6 mm² would do.
Limits and cautions
- Copper or aluminium cables with PVC (70 °C) or EPR/XLPE (90 °C) insulation, in methods A1 to G of NBR 5410 (IEC 60364-5-52). For houses and flats, use the residential cable sizing.
- Shock protection uses the conventional method (80 % of U0 at the origin); selectivity and the breaker I²t come from the manufacturer.
- It is a design aid: it does not replace the electrical design signed by a responsible engineer.
Technical basis
NBR 5410:2004 (aligned with IEC 60364-5-52): minimum section (table 47), current-carrying capacity (tables 36 to 39 with the corrections of tables 40 to 45), coordination of cable and breaker (5.3.4), voltage drop (6.2.7) with the maximum resistance of NBR NM 280 (IEC 60228) and the reactance, short-circuit withstand (5.3.5, table 30), shock protection by automatic disconnection (5.1.2.2.4), neutral with harmonics (6.2.5.6.1 and annex F) and motor circuits (6.5.1.3: service factor and drop at start).
- ABNT NBR 5410 — low-voltage electrical installations
- ABNT NBR NM 280 (IEC 60228) — conductors of insulated cables
- IEC 60364-5-52 — selection and erection of wiring systems
In the full version, you can
- Size three-phase, single-phase and DC circuits from power or current.
- Choose the installation method A1 to G, temperature, grouping, copper or aluminium, PVC or XLPE and parallel cables.
- See the section each criterion requires, the nearby sections with Iz and drop, the neutral, the PE and the length.
- Export an unbranded PDF report and keep the work on your device or in your account, to open it on another device.
ALOGY Tools subscription
One plan unlocks every subscription tool, with PDF reports and work kept in your account, to open on your phone and computer.
- Every subscription tool, in Portuguese, English and Spanish
- Pix or card on Asaas’s secure page, no boleto
- 7 days to withdraw with a full refund; after that, cancel renewal whenever you want
Frequently asked questions
Is the distance out and back?
No. Enter only the one-way length along the real cable route. The factor k already accounts for the return: √3 in three-phase and 2 in single-phase and DC. The length to buy multiplies by the conductors and adds the slack.
Why did the tool give a larger cable than the voltage drop needs?
Because the section must meet every criterion. Short cables with high current are decided by the current-carrying capacity; long cables, by the drop; circuits near the transformer, by the short circuit.
Can I enter the breaker that is already installed?
Yes. The cable is chosen so that Iz is at least the given In. A breaker smaller than the design current is refused, because it would trip in normal use.