Residential cable sizing: cable, breaker and RCD based on Brazilian NBR 5410
Register the whole house — service entrance, panels, RCDs, SPD, rooms and circuits — and see the distribution tree with what meets the criteria, what needs adjustment and what is still to be checked. For a single circuit (shower, outlets, air conditioner), the quick calculation gives cable, breaker, RCD and the diagram with the conductor colours.
Where it helps at work
- Check the circuits of an existing house without losing the record of what is installed, and compare them with a checked proposal.
- See the effect of a new shower or air conditioner on the panel, the feeder and the service entrance breaker.
- Plan the circuits of a refurbishment, with smaller-section branches, RCD groups and sub-panels.
- Show the client, with the tree and the report, why the cable or the RCD has to change.
Worked example: 5500 W shower at 220 V
A 5500 W electric shower at 220 V (two phases) is in the bathroom, 12 m from the panel. The conductors run alone in a conduit embedded in the wall, at 30 °C. Which cable, breaker and RCD?
| Circuit | Electric shower |
|---|---|
| Room | Bathroom |
| Supply | 220 V · phase and phase |
| Power | 5500 W |
| Length (one way) | 12 m |
| Installation | Embedded in conduit (B1) |
| Design current | 26.3 A |
|---|---|
| Cable | 4 mm² |
| Breaker | 32 A · curve B · two-pole |
| Residual-current device | 30 mA · 40 A · required |
| Corrected cable capacity | 32 A |
| Voltage drop | 3.73 V (1.7 %) |
How to read it
The shower draws 25 A at 220 V; with the voltage at the top of the normal range (231 V, 5 % above), it reaches 26.3 A, the design current. A 2.5 mm² cable would carry only 24 A, less than the 32 A breaker: the current-carrying capacity leads to the 4 mm² cable. The 1.7 % drop is well below the 4 % of a final circuit, and the 30 mA RCD is required because it is a bathroom.
Limits and cautions
- Copper conductors with PVC insulation, as in houses and flats. For motors and industrial installations, use the industrial cable sizing.
- Short circuit only with the prospective current given by the utility; let-through energy (I²t), selectivity and earthing depend on the manufacturer and the design. The service entrance category follows the utility’s standard.
- It is a design aid: “meets the checked criteria” is not a compliance certificate and does not replace the electrical design signed by a responsible engineer.
Technical basis
Brazilian NBR 5410 (aligned with IEC 60364): current-carrying capacity with temperature and grouping corrections, minimum sections, coordination with the breaker (NBR NM 60898), voltage drop, 30 mA RCD and conductor colours.
- ABNT NBR 5410 — low-voltage electrical installations
- ABNT NBR NM 60898 — circuit-breakers for household installations
- IEC 60364-5-52 — selection and erection of wiring systems
Frequently asked questions
Can I use a larger breaker so it does not trip?
No. The breaker protects the cable: it must be at most the current the cable can carry. If it trips, the circuit needs a larger cable or another split of the loads.
Does the RCD replace the breaker?
No. The RCD protects people against electric shock; the breaker protects the cable against overload and short circuit. Where the standard requires it, both are used together.
Why did my shower cable come out larger than usual?
Because the tool takes the shower current with the voltage at the top of the normal range (5 % above nominal), when it draws more, and checks the current the cable carries embedded in the wall, with grouping and temperature, and the voltage drop over the real length. Check the shower manual as well and use the larger.