Type T thermocouple table: mV vs °C (−270 to 400 °C)
Type T thermocouple voltage in mV from −270 to 400 °C in 10 °C steps, from the NIST (ITS-90) reference functions with the reference junction at 0 °C.
A type T thermocouple (copper (+) and copper-nickel, constantan (−)) produces a voltage that depends on the temperature difference between the measuring junction and the reference junction. The table follows the NIST (ITS-90) reference functions, with the reference junction at 0 °C.
| °C | mV |
|---|---|
| −270 | −6.258 |
| −260 | −6.232 |
| −250 | −6.180 |
| −240 | −6.105 |
| −230 | −6.007 |
| −220 | −5.888 |
| −210 | −5.753 |
| −200 | −5.603 |
| −190 | −5.439 |
| −180 | −5.261 |
| −170 | −5.070 |
| −160 | −4.865 |
| −150 | −4.648 |
| −140 | −4.419 |
| −130 | −4.177 |
| −120 | −3.923 |
| −110 | −3.657 |
| −100 | −3.379 |
| −90 | −3.089 |
| −80 | −2.788 |
| −70 | −2.476 |
| −60 | −2.153 |
| −50 | −1.819 |
| −40 | −1.475 |
| −30 | −1.121 |
| −20 | −0.757 |
| −10 | −0.383 |
| 0 | 0.000 |
| 10 | 0.391 |
| 20 | 0.790 |
| 30 | 1.196 |
| 40 | 1.612 |
| 50 | 2.036 |
| 60 | 2.468 |
| 70 | 2.909 |
| 80 | 3.358 |
| 90 | 3.814 |
| 100 | 4.279 |
| 110 | 4.750 |
| 120 | 5.228 |
| 130 | 5.714 |
| 140 | 6.206 |
| °C | mV |
|---|---|
| 150 | 6.704 |
| 160 | 7.209 |
| 170 | 7.720 |
| 180 | 8.237 |
| 190 | 8.759 |
| 200 | 9.288 |
| 210 | 9.822 |
| 220 | 10.362 |
| 230 | 10.907 |
| 240 | 11.458 |
| 250 | 12.013 |
| 260 | 12.574 |
| 270 | 13.139 |
| 280 | 13.709 |
| 290 | 14.283 |
| 300 | 14.862 |
| 310 | 15.445 |
| 320 | 16.032 |
| 330 | 16.624 |
| 340 | 17.219 |
| 350 | 17.819 |
| 360 | 18.422 |
| 370 | 19.030 |
| 380 | 19.641 |
| 390 | 20.255 |
| 400 | 20.872 |
What about the cold junction?
In the field the reference junction sits at the transmitter or instrument terminals, almost never at 0 °C. So the voltage measured at the terminals is not the table value: the instrument compensates the cold junction. To check a mV reading, take the terminal temperature into account.
Calculated reference values, not measurements. The thermocouple tolerance depends on its class (IEC 60584-1) and is not in the table.
Values calculated from the reference functions; they do not replace measurement or a calibration certificate.