Type T thermocouple table: mV vs °C (−270 to 400 °C)

Type T thermocouple voltage in mV from −270 to 400 °C in 10 °C steps, from the NIST (ITS-90) reference functions with the reference junction at 0 °C.

A type T thermocouple (copper (+) and copper-nickel, constantan (−)) produces a voltage that depends on the temperature difference between the measuring junction and the reference junction. The table follows the NIST (ITS-90) reference functions, with the reference junction at 0 °C.

Type T thermocouple, reference junction at 0 °C: −270 … 140 °C
°CmV
−270−6.258
−260−6.232
−250−6.180
−240−6.105
−230−6.007
−220−5.888
−210−5.753
−200−5.603
−190−5.439
−180−5.261
−170−5.070
−160−4.865
−150−4.648
−140−4.419
−130−4.177
−120−3.923
−110−3.657
−100−3.379
−90−3.089
−80−2.788
−70−2.476
−60−2.153
−50−1.819
−40−1.475
−30−1.121
−20−0.757
−10−0.383
00.000
100.391
200.790
301.196
401.612
502.036
602.468
702.909
803.358
903.814
1004.279
1104.750
1205.228
1305.714
1406.206
Type T thermocouple, reference junction at 0 °C: 150 … 400 °C
°CmV
1506.704
1607.209
1707.720
1808.237
1908.759
2009.288
2109.822
22010.362
23010.907
24011.458
25012.013
26012.574
27013.139
28013.709
29014.283
30014.862
31015.445
32016.032
33016.624
34017.219
35017.819
36018.422
37019.030
38019.641
39020.255
40020.872

What about the cold junction?

In the field the reference junction sits at the transmitter or instrument terminals, almost never at 0 °C. So the voltage measured at the terminals is not the table value: the instrument compensates the cold junction. To check a mV reading, take the terminal temperature into account.

Calculated reference values, not measurements. The thermocouple tolerance depends on its class (IEC 60584-1) and is not in the table.

Values calculated from the reference functions; they do not replace measurement or a calibration certificate.