Type R thermocouple table: mV vs °C (−50 to 1768.1 °C)
Type R thermocouple voltage in mV from −50 to 1768.1 °C in 10 °C steps, from the NIST (ITS-90) reference functions with the reference junction at 0 °C.
A type R thermocouple (platinum with 13% rhodium (+) and platinum (−)) produces a voltage that depends on the temperature difference between the measuring junction and the reference junction. The table follows the NIST (ITS-90) reference functions, with the reference junction at 0 °C.
Types R and S have close values and the same cable colors; confirm the type configured in the instrument before using the table.
| °C | mV |
|---|---|
| −50 | −0.226 |
| −40 | −0.188 |
| −30 | −0.145 |
| −20 | −0.100 |
| −10 | −0.051 |
| 0 | 0.000 |
| 10 | 0.054 |
| 20 | 0.111 |
| 30 | 0.171 |
| 40 | 0.232 |
| 50 | 0.296 |
| 60 | 0.363 |
| 70 | 0.431 |
| 80 | 0.501 |
| 90 | 0.573 |
| 100 | 0.647 |
| 110 | 0.723 |
| 120 | 0.800 |
| 130 | 0.879 |
| 140 | 0.959 |
| 150 | 1.041 |
| 160 | 1.124 |
| 170 | 1.208 |
| 180 | 1.294 |
| 190 | 1.381 |
| 200 | 1.469 |
| 210 | 1.558 |
| 220 | 1.648 |
| 230 | 1.739 |
| 240 | 1.831 |
| 250 | 1.923 |
| 260 | 2.017 |
| 270 | 2.112 |
| 280 | 2.207 |
| 290 | 2.304 |
| 300 | 2.401 |
| 310 | 2.498 |
| 320 | 2.597 |
| 330 | 2.696 |
| 340 | 2.796 |
| 350 | 2.896 |
| 360 | 2.997 |
| °C | mV |
|---|---|
| 370 | 3.099 |
| 380 | 3.201 |
| 390 | 3.304 |
| 400 | 3.408 |
| 410 | 3.512 |
| 420 | 3.616 |
| 430 | 3.721 |
| 440 | 3.827 |
| 450 | 3.933 |
| 460 | 4.040 |
| 470 | 4.147 |
| 480 | 4.255 |
| 490 | 4.363 |
| 500 | 4.471 |
| 510 | 4.580 |
| 520 | 4.690 |
| 530 | 4.800 |
| 540 | 4.910 |
| 550 | 5.021 |
| 560 | 5.133 |
| 570 | 5.245 |
| 580 | 5.357 |
| 590 | 5.470 |
| 600 | 5.583 |
| 610 | 5.697 |
| 620 | 5.812 |
| 630 | 5.926 |
| 640 | 6.041 |
| 650 | 6.157 |
| 660 | 6.273 |
| 670 | 6.390 |
| 680 | 6.507 |
| 690 | 6.625 |
| 700 | 6.743 |
| 710 | 6.861 |
| 720 | 6.980 |
| 730 | 7.100 |
| 740 | 7.220 |
| 750 | 7.340 |
| 760 | 7.461 |
| 770 | 7.583 |
| 780 | 7.705 |
| °C | mV |
|---|---|
| 790 | 7.827 |
| 800 | 7.950 |
| 810 | 8.073 |
| 820 | 8.197 |
| 830 | 8.321 |
| 840 | 8.446 |
| 850 | 8.571 |
| 860 | 8.697 |
| 870 | 8.823 |
| 880 | 8.950 |
| 890 | 9.077 |
| 900 | 9.205 |
| 910 | 9.333 |
| 920 | 9.461 |
| 930 | 9.590 |
| 940 | 9.720 |
| 950 | 9.850 |
| 960 | 9.980 |
| 970 | 10.111 |
| 980 | 10.242 |
| 990 | 10.374 |
| 1000 | 10.506 |
| 1010 | 10.638 |
| 1020 | 10.771 |
| 1030 | 10.905 |
| 1040 | 11.039 |
| 1050 | 11.173 |
| 1060 | 11.307 |
| 1070 | 11.442 |
| 1080 | 11.578 |
| 1090 | 11.714 |
| 1100 | 11.850 |
| 1110 | 11.986 |
| 1120 | 12.123 |
| 1130 | 12.260 |
| 1140 | 12.397 |
| 1150 | 12.535 |
| 1160 | 12.673 |
| 1170 | 12.812 |
| 1180 | 12.950 |
| 1190 | 13.089 |
| 1200 | 13.228 |
| °C | mV |
|---|---|
| 1210 | 13.367 |
| 1220 | 13.507 |
| 1230 | 13.646 |
| 1240 | 13.786 |
| 1250 | 13.926 |
| 1260 | 14.066 |
| 1270 | 14.207 |
| 1280 | 14.347 |
| 1290 | 14.488 |
| 1300 | 14.629 |
| 1310 | 14.770 |
| 1320 | 14.911 |
| 1330 | 15.052 |
| 1340 | 15.193 |
| 1350 | 15.334 |
| 1360 | 15.475 |
| 1370 | 15.616 |
| 1380 | 15.758 |
| 1390 | 15.899 |
| 1400 | 16.040 |
| 1410 | 16.181 |
| 1420 | 16.323 |
| 1430 | 16.464 |
| 1440 | 16.605 |
| 1450 | 16.746 |
| 1460 | 16.887 |
| 1470 | 17.028 |
| 1480 | 17.169 |
| 1490 | 17.310 |
| 1500 | 17.451 |
| 1510 | 17.591 |
| 1520 | 17.732 |
| 1530 | 17.872 |
| 1540 | 18.012 |
| 1550 | 18.152 |
| 1560 | 18.292 |
| 1570 | 18.431 |
| 1580 | 18.571 |
| 1590 | 18.710 |
| 1600 | 18.849 |
| 1610 | 18.988 |
| 1620 | 19.126 |
| °C | mV |
|---|---|
| 1630 | 19.264 |
| 1640 | 19.402 |
| 1650 | 19.540 |
| 1660 | 19.677 |
| 1670 | 19.814 |
| 1680 | 19.951 |
| 1690 | 20.087 |
| 1700 | 20.222 |
| 1710 | 20.356 |
| 1720 | 20.488 |
| 1730 | 20.620 |
| 1740 | 20.749 |
| 1750 | 20.877 |
| 1760 | 21.003 |
| 1768.1 | 21.103 |
What about the cold junction?
In the field the reference junction sits at the transmitter or instrument terminals, almost never at 0 °C. So the voltage measured at the terminals is not the table value: the instrument compensates the cold junction. To check a mV reading, take the terminal temperature into account.
Calculated reference values, not measurements. The thermocouple tolerance depends on its class (IEC 60584-1) and is not in the table.
Values calculated from the reference functions; they do not replace measurement or a calibration certificate.