Type S thermocouple table: mV vs °C (−50 to 1768.1 °C)
Type S thermocouple voltage in mV from −50 to 1768.1 °C in 10 °C steps, from the NIST (ITS-90) reference functions with the reference junction at 0 °C.
A type S thermocouple (platinum with 10% rhodium (+) and platinum (−)) produces a voltage that depends on the temperature difference between the measuring junction and the reference junction. The table follows the NIST (ITS-90) reference functions, with the reference junction at 0 °C.
Types R and S have close values and the same cable colors; confirm the type configured in the instrument before using the table.
| °C | mV |
|---|---|
| −50 | −0.236 |
| −40 | −0.194 |
| −30 | −0.150 |
| −20 | −0.103 |
| −10 | −0.053 |
| 0 | 0.000 |
| 10 | 0.055 |
| 20 | 0.113 |
| 30 | 0.173 |
| 40 | 0.235 |
| 50 | 0.299 |
| 60 | 0.365 |
| 70 | 0.433 |
| 80 | 0.502 |
| 90 | 0.573 |
| 100 | 0.646 |
| 110 | 0.720 |
| 120 | 0.795 |
| 130 | 0.872 |
| 140 | 0.950 |
| 150 | 1.029 |
| 160 | 1.110 |
| 170 | 1.191 |
| 180 | 1.273 |
| 190 | 1.357 |
| 200 | 1.441 |
| 210 | 1.526 |
| 220 | 1.612 |
| 230 | 1.698 |
| 240 | 1.786 |
| 250 | 1.874 |
| 260 | 1.962 |
| 270 | 2.052 |
| 280 | 2.141 |
| 290 | 2.232 |
| 300 | 2.323 |
| 310 | 2.415 |
| 320 | 2.507 |
| 330 | 2.599 |
| 340 | 2.692 |
| 350 | 2.786 |
| 360 | 2.880 |
| °C | mV |
|---|---|
| 370 | 2.974 |
| 380 | 3.069 |
| 390 | 3.164 |
| 400 | 3.259 |
| 410 | 3.355 |
| 420 | 3.451 |
| 430 | 3.548 |
| 440 | 3.645 |
| 450 | 3.742 |
| 460 | 3.840 |
| 470 | 3.938 |
| 480 | 4.036 |
| 490 | 4.134 |
| 500 | 4.233 |
| 510 | 4.332 |
| 520 | 4.432 |
| 530 | 4.532 |
| 540 | 4.632 |
| 550 | 4.732 |
| 560 | 4.833 |
| 570 | 4.934 |
| 580 | 5.035 |
| 590 | 5.137 |
| 600 | 5.239 |
| 610 | 5.341 |
| 620 | 5.443 |
| 630 | 5.546 |
| 640 | 5.649 |
| 650 | 5.753 |
| 660 | 5.857 |
| 670 | 5.961 |
| 680 | 6.065 |
| 690 | 6.170 |
| 700 | 6.275 |
| 710 | 6.381 |
| 720 | 6.486 |
| 730 | 6.593 |
| 740 | 6.699 |
| 750 | 6.806 |
| 760 | 6.913 |
| 770 | 7.020 |
| 780 | 7.128 |
| °C | mV |
|---|---|
| 790 | 7.236 |
| 800 | 7.345 |
| 810 | 7.454 |
| 820 | 7.563 |
| 830 | 7.673 |
| 840 | 7.783 |
| 850 | 7.893 |
| 860 | 8.003 |
| 870 | 8.114 |
| 880 | 8.226 |
| 890 | 8.337 |
| 900 | 8.449 |
| 910 | 8.562 |
| 920 | 8.674 |
| 930 | 8.787 |
| 940 | 8.900 |
| 950 | 9.014 |
| 960 | 9.128 |
| 970 | 9.242 |
| 980 | 9.357 |
| 990 | 9.472 |
| 1000 | 9.587 |
| 1010 | 9.703 |
| 1020 | 9.819 |
| 1030 | 9.935 |
| 1040 | 10.051 |
| 1050 | 10.168 |
| 1060 | 10.285 |
| 1070 | 10.403 |
| 1080 | 10.520 |
| 1090 | 10.638 |
| 1100 | 10.757 |
| 1110 | 10.875 |
| 1120 | 10.994 |
| 1130 | 11.113 |
| 1140 | 11.232 |
| 1150 | 11.351 |
| 1160 | 11.471 |
| 1170 | 11.590 |
| 1180 | 11.710 |
| 1190 | 11.830 |
| 1200 | 11.951 |
| °C | mV |
|---|---|
| 1210 | 12.071 |
| 1220 | 12.191 |
| 1230 | 12.312 |
| 1240 | 12.433 |
| 1250 | 12.554 |
| 1260 | 12.675 |
| 1270 | 12.796 |
| 1280 | 12.917 |
| 1290 | 13.038 |
| 1300 | 13.159 |
| 1310 | 13.280 |
| 1320 | 13.402 |
| 1330 | 13.523 |
| 1340 | 13.644 |
| 1350 | 13.766 |
| 1360 | 13.887 |
| 1370 | 14.009 |
| 1380 | 14.130 |
| 1390 | 14.251 |
| 1400 | 14.373 |
| 1410 | 14.494 |
| 1420 | 14.615 |
| 1430 | 14.736 |
| 1440 | 14.857 |
| 1450 | 14.978 |
| 1460 | 15.099 |
| 1470 | 15.220 |
| 1480 | 15.341 |
| 1490 | 15.461 |
| 1500 | 15.582 |
| 1510 | 15.702 |
| 1520 | 15.822 |
| 1530 | 15.942 |
| 1540 | 16.062 |
| 1550 | 16.182 |
| 1560 | 16.301 |
| 1570 | 16.420 |
| 1580 | 16.539 |
| 1590 | 16.658 |
| 1600 | 16.777 |
| 1610 | 16.895 |
| 1620 | 17.013 |
| °C | mV |
|---|---|
| 1630 | 17.131 |
| 1640 | 17.249 |
| 1650 | 17.366 |
| 1660 | 17.483 |
| 1670 | 17.600 |
| 1680 | 17.717 |
| 1690 | 17.832 |
| 1700 | 17.947 |
| 1710 | 18.061 |
| 1720 | 18.174 |
| 1730 | 18.285 |
| 1740 | 18.395 |
| 1750 | 18.503 |
| 1760 | 18.609 |
| 1768.1 | 18.694 |
What about the cold junction?
In the field the reference junction sits at the transmitter or instrument terminals, almost never at 0 °C. So the voltage measured at the terminals is not the table value: the instrument compensates the cold junction. To check a mV reading, take the terminal temperature into account.
Calculated reference values, not measurements. The thermocouple tolerance depends on its class (IEC 60584-1) and is not in the table.
Values calculated from the reference functions; they do not replace measurement or a calibration certificate.