Type J thermocouple table: mV vs °C (−210 to 1200 °C)

Type J thermocouple voltage in mV from −210 to 1200 °C in 10 °C steps, from the NIST (ITS-90) reference functions with the reference junction at 0 °C.

A type J thermocouple (iron (+) and copper-nickel, constantan (−)) produces a voltage that depends on the temperature difference between the measuring junction and the reference junction. The table follows the NIST (ITS-90) reference functions, with the reference junction at 0 °C.

Type J thermocouple, reference junction at 0 °C: −210 … 200 °C
°CmV
−210−8.095
−200−7.890
−190−7.659
−180−7.403
−170−7.123
−160−6.821
−150−6.500
−140−6.159
−130−5.801
−120−5.426
−110−5.037
−100−4.633
−90−4.215
−80−3.786
−70−3.344
−60−2.893
−50−2.431
−40−1.961
−30−1.482
−20−0.995
−10−0.501
00.000
100.507
201.019
301.537
402.059
502.585
603.116
703.650
804.187
904.726
1005.269
1105.814
1206.360
1306.909
1407.459
1508.010
1608.562
1709.115
1809.669
19010.224
20010.779
Type J thermocouple, reference junction at 0 °C: 210 … 620 °C
°CmV
21011.334
22011.889
23012.445
24013.000
25013.555
26014.110
27014.665
28015.219
29015.773
30016.327
31016.881
32017.434
33017.986
34018.538
35019.090
36019.642
37020.194
38020.745
39021.297
40021.848
41022.400
42022.952
43023.504
44024.057
45024.610
46025.164
47025.720
48026.276
49026.834
50027.393
51027.953
52028.516
53029.080
54029.647
55030.216
56030.788
57031.362
58031.939
59032.519
60033.102
61033.689
62034.279
Type J thermocouple, reference junction at 0 °C: 630 … 1040 °C
°CmV
63034.873
64035.470
65036.071
66036.675
67037.284
68037.896
69038.512
70039.132
71039.755
72040.382
73041.012
74041.645
75042.281
76042.919
77043.559
78044.203
79044.848
80045.494
81046.141
82046.786
83047.431
84048.074
85048.715
86049.353
87049.989
88050.622
89051.251
90051.877
91052.500
92053.119
93053.735
94054.347
95054.956
96055.561
97056.164
98056.763
99057.360
100057.953
101058.545
102059.134
103059.721
104060.307
Type J thermocouple, reference junction at 0 °C: 1050 … 1200 °C
°CmV
105060.890
106061.473
107062.054
108062.634
109063.214
110063.792
111064.370
112064.948
113065.525
114066.102
115066.679
116067.255
117067.831
118068.406
119068.980
120069.553

What about the cold junction?

In the field the reference junction sits at the transmitter or instrument terminals, almost never at 0 °C. So the voltage measured at the terminals is not the table value: the instrument compensates the cold junction. To check a mV reading, take the terminal temperature into account.

Calculated reference values, not measurements. The thermocouple tolerance depends on its class (IEC 60584-1) and is not in the table.

Values calculated from the reference functions; they do not replace measurement or a calibration certificate.