Type E thermocouple table: mV vs °C (−270 to 1000 °C)
Type E thermocouple voltage in mV from −270 to 1000 °C in 10 °C steps, from the NIST (ITS-90) reference functions with the reference junction at 0 °C.
A type E thermocouple (nickel-chromium (+) and copper-nickel, constantan (−)) produces a voltage that depends on the temperature difference between the measuring junction and the reference junction. The table follows the NIST (ITS-90) reference functions, with the reference junction at 0 °C.
| °C | mV |
|---|---|
| −270 | −9.835 |
| −260 | −9.797 |
| −250 | −9.718 |
| −240 | −9.604 |
| −230 | −9.455 |
| −220 | −9.274 |
| −210 | −9.063 |
| −200 | −8.825 |
| −190 | −8.561 |
| −180 | −8.273 |
| −170 | −7.963 |
| −160 | −7.632 |
| −150 | −7.279 |
| −140 | −6.907 |
| −130 | −6.516 |
| −120 | −6.107 |
| −110 | −5.681 |
| −100 | −5.237 |
| −90 | −4.777 |
| −80 | −4.302 |
| −70 | −3.811 |
| −60 | −3.306 |
| −50 | −2.787 |
| −40 | −2.255 |
| −30 | −1.709 |
| −20 | −1.152 |
| −10 | −0.582 |
| 0 | 0.000 |
| 10 | 0.591 |
| 20 | 1.192 |
| 30 | 1.801 |
| 40 | 2.420 |
| 50 | 3.048 |
| 60 | 3.685 |
| 70 | 4.330 |
| 80 | 4.985 |
| 90 | 5.648 |
| 100 | 6.319 |
| 110 | 6.998 |
| 120 | 7.685 |
| 130 | 8.379 |
| 140 | 9.081 |
| °C | mV |
|---|---|
| 150 | 9.789 |
| 160 | 10.503 |
| 170 | 11.224 |
| 180 | 11.951 |
| 190 | 12.684 |
| 200 | 13.421 |
| 210 | 14.164 |
| 220 | 14.912 |
| 230 | 15.664 |
| 240 | 16.420 |
| 250 | 17.181 |
| 260 | 17.945 |
| 270 | 18.713 |
| 280 | 19.484 |
| 290 | 20.259 |
| 300 | 21.036 |
| 310 | 21.817 |
| 320 | 22.600 |
| 330 | 23.386 |
| 340 | 24.174 |
| 350 | 24.964 |
| 360 | 25.757 |
| 370 | 26.552 |
| 380 | 27.348 |
| 390 | 28.146 |
| 400 | 28.946 |
| 410 | 29.747 |
| 420 | 30.550 |
| 430 | 31.354 |
| 440 | 32.159 |
| 450 | 32.965 |
| 460 | 33.772 |
| 470 | 34.579 |
| 480 | 35.387 |
| 490 | 36.196 |
| 500 | 37.005 |
| 510 | 37.815 |
| 520 | 38.624 |
| 530 | 39.434 |
| 540 | 40.243 |
| 550 | 41.053 |
| 560 | 41.862 |
| °C | mV |
|---|---|
| 570 | 42.671 |
| 580 | 43.479 |
| 590 | 44.286 |
| 600 | 45.093 |
| 610 | 45.900 |
| 620 | 46.705 |
| 630 | 47.509 |
| 640 | 48.313 |
| 650 | 49.116 |
| 660 | 49.917 |
| 670 | 50.718 |
| 680 | 51.517 |
| 690 | 52.315 |
| 700 | 53.112 |
| 710 | 53.908 |
| 720 | 54.703 |
| 730 | 55.497 |
| 740 | 56.289 |
| 750 | 57.080 |
| 760 | 57.870 |
| 770 | 58.659 |
| 780 | 59.446 |
| 790 | 60.232 |
| 800 | 61.017 |
| 810 | 61.801 |
| 820 | 62.583 |
| 830 | 63.364 |
| 840 | 64.144 |
| 850 | 64.922 |
| 860 | 65.698 |
| 870 | 66.473 |
| 880 | 67.246 |
| 890 | 68.017 |
| 900 | 68.787 |
| 910 | 69.554 |
| 920 | 70.319 |
| 930 | 71.082 |
| 940 | 71.844 |
| 950 | 72.603 |
| 960 | 73.360 |
| 970 | 74.115 |
| 980 | 74.869 |
| °C | mV |
|---|---|
| 990 | 75.621 |
| 1000 | 76.373 |
What about the cold junction?
In the field the reference junction sits at the transmitter or instrument terminals, almost never at 0 °C. So the voltage measured at the terminals is not the table value: the instrument compensates the cold junction. To check a mV reading, take the terminal temperature into account.
Calculated reference values, not measurements. The thermocouple tolerance depends on its class (IEC 60584-1) and is not in the table.
Values calculated from the reference functions; they do not replace measurement or a calibration certificate.