PT100 and PT1000 table: resistance vs temperature (−200 to 850 °C)

PT100 and PT1000 resistance from −200 to 850 °C in 10 °C steps, from the IEC 60751 curve (α = 0.00385). Nominal element values, without the leads.

A PT100 is a platinum sensor with 100 Ω at 0 °C; a PT1000 has 1000 Ω. Resistance rises with temperature along the Callendar–Van Dusen curve of IEC 60751:2022, with α = 0.00385 °C⁻¹. The table shows the nominal element value every 10 °C.

Nominal element resistance: −200 … 60 °C
°CPT100 (Ω)PT1000 (Ω)
−20018.52185.20
−19022.83228.25
−18027.10270.96
−17031.34313.35
−16035.54355.43
−15039.72397.23
−14043.88438.76
−13048.00480.05
−12052.11521.10
−11056.19561.93
−10060.26602.56
−9064.30643.00
−8068.33683.25
−7072.33723.35
−6076.33763.28
−5080.31803.06
−4084.27842.71
−3088.22882.22
−2092.16921.60
−1096.09960.86
0100.001000.00
10103.901039.03
20107.791077.94
30111.671116.73
40115.541155.41
50119.401193.97
60123.241232.42
Nominal element resistance: 70 … 330 °C
°CPT100 (Ω)PT1000 (Ω)
70127.081270.75
80130.901308.97
90134.711347.07
100138.511385.06
110142.291422.93
120146.071460.68
130149.831498.32
140153.581535.84
150157.331573.25
160161.051610.54
170164.771647.72
180168.481684.78
190172.171721.73
200175.861758.56
210179.531795.28
220183.191831.88
230186.841868.36
240190.471904.73
250194.101940.98
260197.711977.12
270201.312013.14
280204.902049.05
290208.482084.84
300212.052120.52
310215.612156.08
320219.152191.52
330222.682226.85
Nominal element resistance: 340 … 600 °C
°CPT100 (Ω)PT1000 (Ω)
340226.212262.06
350229.722297.16
360233.212332.14
370236.702367.01
380240.182401.76
390243.642436.40
400247.092470.92
410250.532505.33
420253.962539.62
430257.382573.79
440260.782607.85
450264.182641.79
460267.562675.62
470270.932709.33
480274.292742.93
490277.642776.41
500280.982809.78
510284.302843.03
520287.622876.16
530290.922909.18
540294.212942.08
550297.492974.87
560300.753007.54
570304.013040.10
580307.253072.54
590310.493104.87
600313.713137.08
Nominal element resistance: 610 … 850 °C
°CPT100 (Ω)PT1000 (Ω)
610316.923169.18
620320.123201.16
630323.303233.02
640326.483264.77
650329.643296.40
660332.793327.92
670335.933359.32
680339.063390.61
690342.183421.78
700345.283452.84
710348.383483.78
720351.463514.60
730354.533545.31
740357.593575.90
750360.643606.38
760363.673636.74
770366.703666.99
780369.713697.12
790372.713727.14
800375.703757.04
810378.683786.83
820381.653816.50
830384.603846.05
840387.553875.49
850390.483904.81

How to use the table

  • To check a sensor, measure its resistance disconnected from the transmitter and compare it with the process temperature or a reference bath.
  • With 2 wires, the lead resistance adds to the reading and the instrument shows a higher temperature than the real one.
  • Between two table points the curve is not exactly straight: linear interpolation gives an approximation.

Calculated nominal values, not measurements. The sensor tolerance depends on its class (AA, A, B or C) and is not in the table.

Values calculated from the reference functions; they do not replace measurement or a calibration certificate.