4–20 mA table: current vs percentage of range (and 1–5 V)

4 to 20 mA current for every 5% of range, voltage across a 250 Ω resistor (1 to 5 V) and percentage for every mA, with the NAMUR NE 43 failure limits.

In a 4–20 mA signal, 4 mA is 0% of the configured range (LRV) and 20 mA is 100% (URV). The relationship is linear: each 1% of range is worth 0.16 mA. Many input cards read the current across a 250 Ω resistor, giving 1 to 5 V.

Percentage of range → current and voltage across 250 Ω
% of rangemAV across 250 Ω
04.001.000
54.801.200
105.601.400
156.401.600
207.201.800
258.002.000
308.802.200
359.602.400
4010.402.600
4511.202.800
5012.003.000
5512.803.200
6013.603.400
6514.403.600
7015.203.800
7516.004.000
8016.804.200
8517.604.400
9018.404.600
9519.204.800
10020.005.000
Current → percentage of range
mA% of range
40.00
56.25
612.50
718.75
825.00
931.25
1037.50
1143.75
1250.00
1356.25
1462.50
1568.75
1675.00
1781.25
1887.50
1993.75
20100.00

Outside 4 to 20 mA

Below 4 mA or above 20 mA the signal has left the range: it may be saturation, a transmitter failure or a loop problem. Transmitters configured for NAMUR NE 43 measure from 3.8 to 20.5 mA and signal a failure with 3.6 mA or less, or 21 mA or more. Zero or almost zero means an open loop or no supply.

The percentages apply to any range. To get to the process unit (bar, °C, m³/h), use the endpoints configured in the instrument.

Values calculated from the reference functions; they do not replace measurement or a calibration certificate.